DeDietrich G25 Servisní příručka Strana 71

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 92
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 70
71
15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
15. Maintenance
15.2.2 Setting the ignition electrode
- Check the setting of the ignition electrode
.
Set the gap between the
ignition electrodes: 3 to 4 mm
.
15.2.3 Checking the hydraulic pressure
The hydraulic pressure must be a minimum of 0.8 bars
.
We
recommend filling the installation to around 1.5 bars higher than the
static height
.
15.2.4 Checking the ionization current
` Tilt the flap on the control panel
.
` Press key
%O
and
$P
simultaneously for 2 seconds
.
` Use keys + and - to switch from
to
-
:
Maximum boiler output
-
:
Minimum output
` In the display area:
EMISSION MES. 88.8°: Boiler temperature
EMISSION MES. 8888: Fan speed
EMISSION MES. 88.8uA: Ionization current
Zobrazit stránku 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 91 92

Komentáře k této Příručce

Žádné komentáře